Input Voltage (DC) 40 V to 60 V
Output Voltage (DC) 42 V to 52.5 V
Floating Charge Voltage Setting Range 48 V to 58 V
Equalizing Charge Voltage Setting Range 48 V to 58 V
Charging Current (Each Port) ≥ 300 A
Discharging Current (Each Port) ≥ 300 A
Voltage Drop (max) ≤ 400 mV
Noise Voltage (Peak to Peak) ≤ 400 mV
Battery Port Number (Pcs) 4 Ports
Capacity per Battery Pack ≤ 1000 Ah
Efficiency ≥ 98%
Standby Power Consumption ≤ 10 W
Working Ambient Temperature -15ºC to 55ºC
Storage Ambient Temperature -40ºC to 75ºC
Communication Protocol RS485/CAN
Dimensions (mm): W = 442, D = 350, H = 87.5 (2U)
Weight ≤ 6.5 kg
●Temperature compensation for VRLA Batteries.
●Synchronous and asynchronous modes of charging/discharging.
●No outage on transition or on controller fault. (default port continuity)
●Genset control (start on Voltage threshold and stop on battery charging current threshold).
●Auto CP and Genset variable charging current settings.
●The technical parameters of each battery port for differential battery packs could be set independently.
●Support installation on walls, cable ladder, and embedded installation.
●Support lithium battery cell over-voltage, under-voltage, over current, overheat cut-off protection.
● Independent charge and discharge current of each battery type.
●Support RS485/CAN communication with lithium batteries.
●Real-Time Monitoring of operating parameters(SOC/SOH/DOD)of each battery.
●Password Protected colored Display.
● Independent float and equalize charge voltage of each battery type.
●Support the sharing of lead-acid batteries, lithium batteries, and supercapacitors.
●Support lithium batteries for preferential discharging and lead-acid batteries as a backup.
#Hybrid #Battery #Controller #HBC #AGG #Network #Solutions #HNL